Investigation of the effect of layered structure on partial discharges in transformer pressboard insulator

dc.authorid0000-0002-3399-9346
dc.contributor.authorUğur, Mukden
dc.contributor.authorAtalar, Fatih
dc.contributor.authorÖnhon, N.Özben
dc.date.accessioned2024-04-04T13:50:45Z
dc.date.available2024-04-04T13:50:45Z
dc.date.issued2023
dc.departmentTAÜ, Fen Bilimleri Enstitüsü, Robotlar ve Akıllı Sistemler Ana Bilim Dalı Koleksiyonuen_US
dc.description.abstractThe dielectric performance of pressboards impregnated with mineral oil is one of the key points in regard to the quality of the transformer’s working life. Partial discharges (PDs) occurring in the pressboard can cause some insulation defects which might be one of the major reasons for an electrical breakdown. Detection of the PDs in pressboards gives a chance to understand the dielectric behavior of the insulators, hence major defects can be prevented just in early stage. The main point of the study is to investigate the differences in dielectric performance of layered and non-layered pressboards in the presence of PDs. For this purpose, the PD behavior of a layered pressboard with three layers (each with a thickness of 0.5 mm) and of a non-layered (solid) pressboard (with a thickness of 1.5 mm) is examined for two different high voltage levels (20 and 30 kV). To detect the PDs, Hall Effect Sensors are employed, considering that PDs cause fluctuations in the magnetic field. To analyze the magnetic field measurements from a statistical point of view, the Kaplan–Meier method and the Weibull analysis are used.
dc.identifier.citationUğur, M., Atalar, F., Önhon, N.Ö. (2023). Investigation of the effect of layered structure on partial discharges in transformer pressboard insulator. Electrical Engineering içerisinde 105, 3459-3467.
dc.identifier.doi10.1007/s00202-023-01903-6
dc.identifier.endpage3467en_US
dc.identifier.issue105en_US
dc.identifier.scopus2-s2.0-85162904754
dc.identifier.startpage3459en_US
dc.identifier.urihttps://hdl.handle.net/20.500.12846/1003
dc.identifier.wosWOS:001016157500003
dc.indekslendigikaynakScopus
dc.language.isoen
dc.publisherSpringer
dc.relation.ispartofElectrical Engineering
dc.relation.publicationcategoryMakale - Uluslararası Hakemli Dergi - Kurum Öğretim Elemanı
dc.rightsinfo:eu-repo/semantics/openAccess
dc.subjectLayered pressboardsen_US
dc.subjectNon-layered pressboardsen_US
dc.subjectPartial dischargeen_US
dc.subjectKaplan–Meier methoden_US
dc.subjectWeibull analysisen_US
dc.titleInvestigation of the effect of layered structure on partial discharges in transformer pressboard insulator
dc.typeArticle

Dosyalar

Orijinal paket
Listeleniyor 1 - 1 / 1
Yükleniyor...
Küçük Resim
İsim:
s00202-023-01903-6.pdf
Boyut:
948.58 KB
Biçim:
Adobe Portable Document Format
Açıklama:
Makale Dosyası
Lisans paketi
Listeleniyor 1 - 1 / 1
[ X ]
İsim:
license.txt
Boyut:
1.44 KB
Biçim:
Item-specific license agreed upon to submission
Açıklama: